Conforms to IEC Standards 60309-1 and 60309-2 Watertight: IP67 per IEC 529 Splashproof: IP54 per IEC 529
Flame Class Rating per UL94: VO for Contact Carriers (insulators) HB or better for Housings (UV Stabilized)
Impact Resistance:
Units conditioned to -25°C for 6 hours and dropped 8 times from 30"
Crush: Units conditioned to -25°C for 6 hours and 250 Ibs. of force applied for 1 minute.
Cable Grip Retention: (applied to min. cable size)
Unit
20A 30A 60A 100A |
Force, Ibs. 30 75 150 150 |
Torque, ft. Ibs. 0.4 0.5 1.0 1.0 |
 | 
Electrical
Dielectric Voltage: 3000V maximum
Maximum Working Voltage: 600 RMS
Current Interrupting:
Certified at full-rated current and voltage
Temperature Rise:
Maximum 30°C temperature at full rated current
Overload:
50 cycles at 150% of rated current and 100% of
rated voltage. (Power factor at .75-.80)
Endurance with Load: (at .75-.80 Power Factor)
| 20A- |
5,000 mated cycles at full-rated
current/voltage. |
| 30A and 60A- |
2,000 mated cycles with full-rated
current/voltage applied on every
other cycle. |
| 100A- |
500 mated cycles with full-rated
current/voltage applied on every
other cycle. |
|